Chart: SL73 High Performance

Higher Weather Performance (Raised) Sill - SL73

Type of Test

Inward Opening Units

Approved with Miami Dade County and FL Product Approval #FL20108

Outward Opening Units

Approved with Miami Dade County and FL Product Approval #FL20107

Air Infiltration 1

Protocol TAS 202 and ASTM E-283, cfm/ft2

@ 1.57 psf (75 Pa): 0.08 to 0.30

A1 to A3 2


@ 6.24 psf (300 Pa):

0.20 to 0.30

@ 1.57 psf (75 Pa): 0.02 to 0.14

A1 to A3 2


@ 6.24 psf (300 Pa):

0.07 to 0.30

Static Water Penetration 1 *

Protocol TAS 202 and ASTM E-547 and E-331

No uncontrolled water entry
@ 9 psf

(440 Pa)

No uncontrolled water entry
@ 9 psf

(440 Pa)

Dynamic Water Penetration 3

AMAA 520 & ASTM E-2268

Performance Level 2:

No water entry above allowable
@ 6-18 psf

(300-860 Pa)

Performance Level 1:

No water entry above allowable
@ 5-15 psf

(250-715 Pa)

Structural Load Deflection 1

TAS 202 & ASTM E-330: pass

Note that the structural test pressures were 50% higher than the design pressures.

design pressure

Positive
@ 70 psf
(3350 Pa)

Negative
@ 100 psf
(4785 Pa)

Class SP-PG70, Panel size - 3’ x 8’

(915 mm x 2362 mm) 2

design pressure

Positive
@ 70 psf
(3350 Pa)

Negative
@ 70 psf
(3350 Pa)

Class SP-PG70, Panel size - 3’ x 8’

(915 mm x 2438 mm) 2

Missile Impact & Cycling 1

Protocols TAS 201 & 203: Pass

ASTM E 1886 &E1996

With either 7/16" single impact or 1 1/8" insulated impact glass*
Design Pressure

Positive
@ 90 psf
(4300 Pa)

Negative
@ 110 psf
(5260 Pa)

With either 7/16" single impact or 1 1/8" insulated impact glass*
Design Pressure

Positive
@ 90 psf
(4300 Pa)

Negative
@ 90 psf
(4300 Pa)

Forced Entry Resistance 1

In accordance with TAS 202, AAMA -1304

and ASTM F842 requirements +F1

1 Excerpts of results of 3 separate units of various panels and configurations tested by Architectural Testing, Inc., Fresno, CA, an independent testing laboratory in October 2009.

2 For Canada, tested to NAFS-08 or equivalent and CSA A44051-09 (with weep holes in sills by others to drain standing water in sill channels).

3 Excerpts of results of 12’11” W x 8’3” H four panel units 1L3R tested by Architectural Testing, Inc., Fresno, CA, an independent testing laboratory in October 2009.

* Water rating may not be applicable for configuration not tested, especially even panels and even panels configurations.

Thermal Performance

(Floor Supported Units)

Rated, certified and labeled in accordance with NFRC 100 + 200

inward opening units outward opening units
Type of Glass (1 lite) Center of Glass U-Factor IG Glass Thickness Unit U-Factor SHGC 3 VT 4 2015 Energy Star Unit U-Factor SHGC 3 VT 4 2015 Energy Star
Double IG Impact
(air filled)
.45 1 1/8”
(28 mm)
.47 .47 .51 ^ .47 .47 .51 ^
Double IG Impact Low E (argon filled) .24 1 1/8”
(28 mm)
.33 .19 .40 ^ .33 .19 .40 ^
Double IG Impact Low E #2 & #4 surfaces (argon filled) .20 1 1/8”
(28 mm)
.30 .18 .39 ^ * .30 .18 .39 ^ *
Single Impact .94 7/16”
(11 mm)
.78 .50 .56 * .79 .50 .56 -
Single Impact Low E (SB70) .94 7/16”
(11 mm)
.78 .25 .39 - .78 .24 .39 -
Single Impact Hard Coat Low E & Low E (SB 70) .60 7/16”
(11 mm)
.57 .21 .43 ^ .58 .21 .43 ^

Notes

3 SHGC = Solar Heat Gain Coefficient

4 VT = Visible Transmittance

^ Both U factor and SHGC meet FL 2015 Energy Code for both commercial and residential sections in both climate zones for operable fenestration.

* 2015 Energy Star Qualification Criteria: U-Factor for doors in all climate zones 30, SHGC 25 in South/South Central zones and 40 in North/North Central zones. (For guidance only. NanaWall is not a participant of the Energy Star program.)

Call NanaWall (800.873.5673 | 415.383.3148) for U-Factor & SHGC for other glass types.